Cassette Four Outlet Fan Coil--Cassie Series
Model Air volume 08*170=1360 m³/h
The body is light and thin, and the thick of its main body is only 290mm. It is installed in the ceiling and does not occupy indoor space at all. It can be widely used in shopping malls, office buildings, hospitals and other places. Ultra-small volume design saves valuable space for you. In addition, it has the advantages of high efficiency, low noise, and convenient installation and maintenance. It is an ideal product for your choice.
KM4 | 1 |
V | 2 |
08 | 3 |
R | 4 |
G | 5 |
EH20 | 6 |
CV2 | 7 |
EDP | 8 |
1. KM4: Cassette four outlets
2. V: two-pipe P: four-pipe
3.Model air volume 08*170=1360 m³/h
4. R: With remote control (standard) W: With wire controller: T: With terminal block
5.G: With group control function M: With MODBUS function
6.EH20: With 2KW electric heating
7. CV2: Cold coil with 2-port valve assembly installed by factory CV3: Cold coil with 3-port valve assembly installed by factory
HV2: Hot coil with 2-port valve assembly installed by factory HV3: Hot coil with 3-port valve assembly installed by factory
8. EDP: With external water tray
Model representation example: KM4V08 means a 2-pipe embedded fan coil unit with a nominal air volume of 1360m³/h.
Features:
1. Multi-directional airflow to make the temperature of the application site more uniform;
2. Both remote control and wire control is acceptable(wire control is optional), and control mode is flexible ;
3. Automatic wind swing, each of the four wind guide blades has a stepping motor to control the swing wind, which is more reliable than the control of the linkage structure;
4. It adopts large-diameter vortex centrifugal fan, which is ultra-quiet operation, environmental protection and energy saving. It has hree-dimensional spiral blades with large inclination angle, and the bearings used in the motor are rolling bearings. The motor shaft is made of quenched and tempered steel, and the surface has been specially treated for rust prevention, which is durable, efficient and energy-saving, ultra-quiet. And EPS foam with good sound absorption further reduce noise;
5. The intelligent high-lift condensate lift pump can make the water level drop up to 750 mm, which greatly facilitates the arrangement of the drainage pipe and eliminates the worries of condensate discharge;
6. Water level switch protection can prevent hidden dangers of water leakage;
7. Fresh air can be introduced from outside to improve indoor air quality;
8. It is easy to maintain with the convenient structure design;
8.1. Remove the return style grille to repair the electric control;
8.2. Remove the air guide ring to repair or replace the wind wheel and motor
9. Exquisite structure, sturdy and durable centrifugal fan, ultra-quiet operation
This series of fan coils adopts galvanized plate casing; the condensed water pan is integrally formed by blister technology, no welds, solder joints, which eliminates the shortcomings of dripping and leakage of the welded water pan; the EPS material is foamed and bonded to the water pan; the body structure is exquisite.
Lightweight design: the body is light and thin with a large number of non-metallic materials, and it is installed on the ceiling, which is both beautiful and safe.
10. High performance, high efficiency
Integral "C"-shaped heat exchanger design is with high density and without intervals, and internal airflow temperature is uniform, which can avoid local air supply temperature differences caused by the uneven secondary mixing of internal air flow caused by the two-fold exchanger.
The heat exchanger adopts high-quality medium Ø9.52mm copper tubes and high-efficiency hydrophilic coated aluminum fins, as well as advanced tube expansion technology, so that the copper tubes and aluminum foil can reach an ideal contact. It is also reinforced heat transfer by a fan with large air volume and low noise, so that the unit can play an ideal heat transfer efficiency.